MVDC Circuit Breakers
(Solid-State and Hybrid)
October 2026
8 / 9
Overview
Medium-Voltage Direct Current (MVDC) circuit breakers interrupt fault current in DC distribution systems using power semiconductors, either alone (solid-state) or paired with a fast mechanical switch (hybrid). AC circuit breakers rely on the AC-waveform zero-crossings to extinguish an arc every half-cycle. Without the AC-waveform, a mechanical breaker cannot interrupt a DC fault fast enough to prevent heat buildup and arcing[1].
Two architectures are covered here. The Solid-State architecture carries current through a semiconductor path, with no moving parts. The Hybrid architecture pairs a fast mechanical switch with a solid-state commutation branch, trading some speed for lower steady-state conduction losses. There is significant interest in both tracks with the emergence of MVDC as a distribution architecture, driven by data centers, locally sourced energy integration, and storage, rather than as a niche shipboard or industrial application[2].
Benefits
Fault Interruption Speed
DTI’s commercial solid-state breakers open in under 700 nanoseconds[3], and ORNL’s prototype interrupted a 1,400-volt fault in under 50 microseconds, four to six times faster than earlier thyristor-based demonstrations[1].
Arc Elimination
Routing fault current through a semiconductor path instead of a mechanical contact gap removes the arcing risk inherent to interrupting DC with a mechanical breaker, directly reducing fire and wildfire risk[1].
Demonstrated Scalability
ORNL connected MVDC breakers in series and validated operation up to 1,800 volts, with a stated roadmap toward 10,000 volts[1]. DTI advertises a 12 kV line rated 750 to 4,000 A[4], although ORNL states that no commercial breaker can handle DC above 2,000 V[1].
Efficiency and Speed Targets in Active Development
The Eaton/CPES/Illinois Institute of Technology program targets 6 kV DC, 200 A, sub-500 microsecond interruption, and greater than 99.99 percent efficiency[5][6][7].
System-level Upside
Wider MVDC adoption reduces the number of AC-DC conversions in a distribution path, lowering conversion losses for DC-native loads and sources such as solar, batteries, and EV charging[2].
Technology Readiness Level (TRL)
- Final system completed
- Tested and validated under expected conditions
- Near operational readiness
- Design essentially finalized
The pilot projects are at an earlier stage. ORNL’s thyristor-based breaker has been bench-tested in series up to 1,800 volts, with scale-up to 10,000 volts still in progress rather than demonstrated[1][8][9]. The two parallel ARPA-E efforts are earlier still: the Eaton/CPES/Illinois Institute of Technology hybrid breaker, awarded in 2022, targets 6 kV as its design point, with no interruption test result or field demonstration identified in available sources[5][6]; Sandia’s gallium nitride-based breaker is described only as targeting “medium to high voltage applications,” without a demonstrated voltage identified[10].
The commercial case, DTI’s 12 kV product, anchors the upper end: a decade of market presence, a published price list, and an active government contract[3][4][7], though without independent confirmation of a specific field installation, and outside the utility distribution segment specifically. The broader academic literature treats circuit breaker topology and semiconductor device selection for MVDC as an open, actively contested research question rather than settled engineering practice[11][12].
Adoption Readiness Level (ARL)
Value Proposition
Delivered Cost
Medium Risk
Pricing appears to scale with design requirements such as voltage and current ratings up to 1 MW nominal load[4], though this reflects a low-volume shipboard/microgrid market rather than utility-scale production, with no fixed cost figures publicly available. No comparable cost data exists yet for the utility-relevant pilot projects; the Eaton/CPES/Illinois Institute of Technology program is still targeting technical performance metrics, not cost[5][6]. ORNL separately notes that prior wide-bandgap semiconductor approaches had been too costly to compete with mechanical breakers, which is why its own program chose lower-cost thyristors[1].
Functionality Performance
Medium Risk
DTI’s commercial breakers switch in under 700 nanoseconds with over 99.7 percent efficiency[3], and ORNL’s prototype achieved sub-50 microsecond interruption at 1,400 volts[1]. The Eaton/CPES/Illinois Institute of Technology efficiency and speed figures (99.99 percent, sub-500 microseconds) remain design targets from a 2022 award rather than demonstrated results[5][6]. Independent academic work on alternative MVDC topologies reflects the same gap: a bidirectional T-source breaker design was verified at medium-voltage level only through simulation, with the experimental prototype limited to low voltage[13]. None of the voltage levels demonstrated to date reach the 15-35 kV range typical of utility distribution feeders.
Ease of Use/Complexity
High Risk
Peer-reviewed literature confirms that DC protection standardization is an unresolved, active effort: the IEC 60255 series is still being developed to cover protection devices with digital inputs and outputs, and national standards bodies have not yet fully integrated it with domestic frameworks[12]. Without settled international standards comparable to IEC 62271-100 or IEEE C37.04 for AC breakers, integrating an MVDC breaker into an existing protection scheme currently requires custom engineering rather than established procedure.
Market Acceptance
Demand Maturity/Market Openness
Medium Risk
Demand is anchored by a real customer relationship: DTI’s ongoing Department of Defense contract, delivered through publicly traded Ideal Power (Nasdaq: IPWR) and NAVSEA[7]. The utility-relevant pilot projects show institutional demand through three independently funded federal programs[1][5][10], and a dedicated commercial market research segment for medium-voltage DC distribution systems already exists[2], but adoption there is still driven by government-funded programs rather than established utility procurement.
Market Size
Low Risk
The MVDC distribution system market is estimated at USD 1.28 billion in 2025, projected to reach USD 2.21 billion by 2032 at a compound annual growth rate of 8.06 percent[2]. The adjacent data center low- and medium-voltage power distribution market, a significant driver of MVDC demand, is estimated at USD 3.8 billion in 2025 and projected to reach USD 10.9 billion by 2035[14].
Downstream Value Chain
Medium Risk
Deployment depends on converter availability and interoperability testing across converters, protection equipment, communications, and supervisory controls, an ecosystem that market analysts describe as still forming rather than mature for MVDC specifically[2]. DTI’s existing shipboard/microgrid customer base does not yet establish a utility-grid downstream channel.
Resource Maturity
Capital Flow
Medium Risk
A Department of Defense contract is flowing through a Nasdaq-listed company (Ideal Power, IPWR) in addition to DTI’s own commercial sales[4][7]. The utility-relevant pilot projects are federally funded through ARPA-E and the DOE Office of Electricity across three independent programs[1][5][6][8][9][10]; no comparable private capital was identified for that side of the technology.
Project Development, Integration, and Management
Medium Risk
DTI has more than a decade of shipped systems and an active Department of Defense contract, a genuine execution track record, even though it is outside the utility distribution segment[3][4][7]. No field-deployed utility MVDC project was identified in the United States; in China, hybrid DC breakers are in service in MVDC distribution projects such as Zhuhai Tangjiawan (±10 kV); the federally funded pilot projects remain at the laboratory or bench-demonstration stage[1][5][6][8][9][10].
Infrastructure
Medium Risk
Circuit breakers are a component technology rather than standalone infrastructure, but broader MVDC adoption depends on compatible converters and coordinated protection across the distribution network, which market analysis describes as still under development rather than mature[2].
Manufacturing and Supply Chain
Medium Risk
Solid-state breaker products have been commercially manufactured and shipped. The utility-relevant pilot projects rely on established semiconductor technologies (thyristors, IGBTs, and silicon carbide and gallium nitride devices) rather than exotic materials[1][10][11], but have no comparable production history.
Materials Sourcing
High Risk
While no rare-earth elements are required, gallium nitride supply chains face meaningful geopolitical concentration risk, with China controlling the substantial majority of gallium production and having demonstrated willingness to weaponize export controls[1][10][11].
Workforce
Medium Risk
Market analysis of MVDC distribution identifies building specialized skills in DC protection and power electronics as a stated priority for the industry, which implies this workforce is not yet established at scale[2].
License to Operate
Regulatory Environment
High Risk
Peer-reviewed literature confirms that DC protection standardization remains an active, unresolved effort. The IEC 60255 series is under development to address protection devices with digital inputs and outputs, and national standards bodies, the cited example being Korea, have adopted IEC standards without full integration into domestic frameworks[12]. No equivalent to the mature AC breaker standards (IEC 62271-100, IEEE C37.04) specifically for MVDC breakers exists yet.
Policy Environment
Low Risk
The technology benefits from active federal support through multiple channels: the Department of Defense’s Rapid Innovation Fund (DTI/Ideal Power/NAVSEA)[7], DOE Office of Electricity funding for ORNL[1][8][9], and ARPA-E funding for both the Eaton/CPES/Illinois Institute of Technology and Sandia programs[5][6][10]. No policy mandate specific to MVDC circuit breakers was identified.
Permitting & Siting
Low Risk
As a component installed within an existing substation, vessel, or facility rather than standalone infrastructure, circuit breakers do not carry independent siting or permitting requirements beyond the facility that houses them.
Environmental & Safety
Low Risk
Eliminating arcing during DC fault interruption is a stated safety motivation for this technology, directly reducing fire and wildfire risk relative to a mechanical breaker attempting to interrupt a DC arc without a natural current zero-crossing[1].
Community Perception
Low Risk
As internal grid or vessel hardware with no direct public-facing footprint, no community opposition or perception risk was identified in the sources reviewed.
Case Studies & Implementation
Diversified Technologies, Inc. (DTI) – Commercial Shipboard and Microgrid Breakers
DTI sells a 12 kV solid-state breaker product line, in production since at least 2013 and refreshed in 2023, priced from $50,000 and scaling up to 1 MW nominal load, used in shipboard and microgrid applications. The line is now being enhanced for higher efficiency under an active Department of Defense contract with Ideal Power (Nasdaq: IPWR) and NAVSEA. This is the clearest commercial-scale case identified, though the evidence is vendor-reported rather than confirmed by an independent case study or government acceptance report of a specific fielded, in-service unit[3][4][7].
Oak Ridge National Laboratory – GRID-C Thyristor-Based Breaker
ORNL’s Grid Research Innovation and Development Center bench-tested a thyristor-based solid-state breaker, connecting units in series and validating operation up to 1,800 volts, interrupting a 1,400-volt fault in under 50 microseconds. The program’s stated roadmap targets scale-up to 10,000 volts, aimed specifically at the voltage and duty cycle relevant to utility DC distribution rather than shipboard or microgrid use. This is the clearest utility-relevant pilot case identified, still short of a field or operational-environment demonstration[1][8][9].
https://www.ornl.gov/news/medium-voltage-circuit-breaker-unlocks-electricity-abundance-savings
References
- ORNL. Medium-voltage circuit breaker unlocks electricity abundance, savings (August 2025). https://www.ornl.gov/news/medium-voltage-circuit-breaker-unlocks-electricity-abundance-savings
- 360iResearch. Medium Voltage DC Distribution System Market, Global Forecast 2026-2032. https://www.360iresearch.com/library/intelligence/medium-voltage-dc-distribution-system
- Military Aerospace. Circuit breakers for military DC power distribution offered by Diversified Technologies (April 2013). https://www.militaryaerospace.com/power/article/16715911/circuit-breakers-for-military-dc-power-distribution-offered-by-diversified-technologies
- PRWeb. Diversified Technologies’ New Solid State Circuit Breaker Opens in Microseconds and Replaces Mechanical Types (June 2023). https://www.prweb.com/releases/diversified-technologies-new-solid-state-circuit-breaker-opens-in-microseconds-amp-replaces-mechanical-types-844472673.html
- ARPA-E. Ultra-Efficient Intelligent MVDC Hybrid Circuit Breaker (Eaton, Virginia Tech CPES, Illinois Institute of Technology). https://arpa-e.energy.gov/programs-and-initiatives/search-all-projects/ultra-efficient-intelligent-mvdc-hybrid-circuit-breaker
- Virginia Tech CPES. Eaton Corporation and Dong Dong awarded DOE project (February 2022). https://cpes.vt.edu/news/news/862
- GlobeNewswire. Ideal Power Signs $1.2 Million Contract to Partner with Diversified Technologies on Demonstration of B-TRAN Enabled High Efficiency DC Circuit Breaker (August 2020). https://www.globenewswire.com/en/news-release/2020/08/10/2075641/0/en/Ideal-Power-Signs-1-2-Million-Contract-to-Partner-with-Diversified-Technologies-on-Demonstration-of-B-TRAN-Enabled-High-Efficiency-Direct-Current-Circuit-Breaker.html
- ORNL. Grid electronics research to bridge gap to cleaner, more reliable power (GRID-C / MERIT initiative). https://www.ornl.gov/news/grid-electronics-research-bridge-gap-cleaner-more-reliable-power
- DOE / OSTI. Kandula, R.P. and Kimpara, M.L.M., SCR-based Medium Voltage DC Solid-State Circuit Breaker, IEEE ECCE 2024 (ORNL). https://www.osti.gov/biblio/3002807
- ARPA-E. ARC-SAFE: Accelerated Response semiconducting Contactors and Surge Attenuation for DC Electrical Systems (Sandia National Laboratories). https://arpa-e.energy.gov/programs-and-initiatives/search-all-projects/arc-safe-accelerated-response-semiconducting-contactors-and-surge-attenuation-dc-electrical-systems
- Rodrigues, R. and Du, Y. A Review of Solid-State Circuit Breakers, IEEE Transactions on Power Electronics, 2021. https://doi.org/10.1109/TPEL.2020.3003358
- Kim, B. and Kim, I. Optimal circuit breaker allocation strategy in DC transmission-connected systems, Scientific Reports (Nature), 2024. https://www.nature.com/articles/s41598-024-74166-1
- Sapkota, S. et al. An improved bidirectional T-source circuit breaker for MVDC, Electrical Engineering (Springer), 2022. https://link.springer.com/article/10.1007/s00202-021-01473-5
- Future Market Insights. Data Center LV/MV Power Distribution Market, Global Forecast 2025-2035. https://www.futuremarketinsights.com/reports/data-center-lvmv-power-distribution-market
If you have any updates or would like to suggest a new technology, please let us know by filling out this form.